6 BASIC INSTRUCTIONS
6.2 Arithmetic Operation Instructions
245
6
D+(P)(_U) [when three operands are set]
These instructions add the two sets of 32-bit binary data specified.
■
Execution condition
Setting data
■
Description, range, data type
• In safety programs executed by the Safety CPU, only safety devices and safety labels of data types described in the table
can be used.
■
Applicable devices
• In safety programs executed by the Safety CPU, only the following safety devices and constants can be used.
Ladder
ST
ENO:=DPLUS(EN,s1,s2,d);
ENO:=DPLUSP(EN,s1,s2,d);
ENO:=DPLUS_U(EN,s1,s2,d);
ENO:=DPLUSP_U(EN,s1,s2,d);
FBD/LD
(
is to be replaced by any of the following: DPLUS, DPLUSP, DPLUS_U, DPLUSP_U.)
Instruction
Execution condition
D+
D+_U
D+P
D+P_U
Operand
Description
Range
Data type
Data type (label)
(s1)
D+(P)
First addend data or the start device where the
first addend data is stored
-2147483648 to 2147483647
32-bit signed binary
ANY32_S
D+(P)_U
0 to 4294967295
32-bit unsigned binary
ANY32_U
(s2)
D+(P)
Second addend data or the start device where
the second addend data is stored
-2147483648 to 2147483647
32-bit signed binary
ANY32_S
D+(P)_U
0 to 4294967295
32-bit unsigned binary
ANY32_U
(d)
D+(P)
Start device for storing the operation result
32-bit signed binary
ANY32_S
D+(P)_U
32-bit unsigned binary
ANY32_U
EN
Execution condition
Bit
BOOL
ENO
Execution result
Bit
BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H E
$
(s1)
(s2)
(d)
Operand
Bit
Word
Constant
SA\X, SA\Y, SA\M, SA\SM, SA\B
SA\T, SA\ST, SA\C, SA\D, SA\W, SA\SD
K, H
(s1)
(s2)
(d)
RnCPU RnENCPU
RnSFCPU RnSFCPU
RnPCPU
RnPCPU
(Standard)
(Safety)
(Redundant)
(Process)
(s1)
(s2)
(d)
EN
ENO
d
s1
s2
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......