11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
1219
11
■
Loop tag past value memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
The loop tag past value memory occupies 32 words after the loop tag memory.
■
Execution cycle (
T)
Set the execution cycle (
T) in SD816 and SD817 in single-precision real number.
Processing details
This instruction calculates the manipulated value (MV) from the input value (E1=
MV) in the device specified by (s1) by
performing input addition processing.
The instruction also turns ON or OFF the device specified by (d1) in proportion to the manipulated value (MV).
The ON/OFF time is a value determined by assuming the time specified by the control output cycle (CTDUTY) as 100%.
The ON/OFF time is switched every execution cycle.
The instruction also performs variation rate & upper/lower limiter and reset windup of the calculated manipulated value (MV).
+68
+69
CTDUTY
Control output
cycle
0 to 999999 [s]
Set a value within the following range.
Single-precision
real number
1.0
User
Operand: (d2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+116
ALM2
Alarm detection
2
MHA2, MLA2
0: No alarm
1: Alarm
System
+118
Control output
cycle counter
initialization
completion flag
+119
Control output
cycle counter
(The value is
rounded off to
the nearest
whole number.)
+120
Output counter
+121
Output ON
counter
(1) Device specified by (d1)
Operand: (d2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
©
T
CTDUTY
<=32767
b15
b0
b1
b2
MHA2
MLA2
...
ON
OFF
MV
BW
t
70%
50%
30%
30%
70%
50%
50%
70%
30%
(1)
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......