1278
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
■
Loop tag memory
The loop tag memory occupies 96 words from the specified start device.
■
Loop tag past value memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
The loop tag past value memory occupies 32 words after the loop tag memory.
Operand: (d2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+1
MODE
Control mode
0 to FFFFH
16-bit unsigned
binary
8H
User/
system
+3
ALM
Alarm detection
0 to FFFFH
SPA
0: Loop RUN
1: Loop STOP
16-bit unsigned
binary
4000H
User/
system
+14
+15
SPR
Set value
-999999 to 999999
Single-precision
real number
0.0
User
+16
+17
BIAS
Bias
-999999 to 999999 [%]
Single-precision
real number
0.0
User
+46
+47
CT
Control cycle
0 to 999999 [s]
Set a value within the following range.
Single-precision
real number
1.0
User
+50
+51
DR
Variation rate
limit value
0 to 999999
Single-precision
real number
100.0
User
+52
+53
RMAX
Ratio upper limit
value
-999999 to 999999
Single-precision
real number
100.0
User
+54
+55
RMIN
Ratio lower limit
value
-999999 to 999999
Single-precision
real number
0.0
User
+56
+57
R
n
Ratio current
value
-999999 to 999999
Single-precision
real number
0.0
System
Operand: (d2)
Position
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+96
Control cycle
counter
initialization
completion flag
System
+97
Control cycle
counter (The
value is rounded
off to the nearest
whole number.)
+98
+99
R
n-1
Last value
b15
b9
b10
b1
b2
b3
b4
b5
b6
b7
b8
b0
CMV
CSV
LCM
LCA
LCC
MAN
AUT
CAS
CMB
CAB
CCB
...
b15b14
b0
...
SPA
©
T
CT
<=32767
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......