15 NETWORK COMMON INSTRUCTIONS
15.2 CC-Link Dedicated Instructions
1527
15
■
Access/attribute code
*1 Any device other than the above cannot be accessed. To access a bit device, specify 0 or a multiple of 16.
*2 When the target station is other than the CC-Link IE Controller Network module and CC-Link IE Field Network master/local module, refer
to the manual of the target station.
*3 None of D65536 and the subsequent extended data registers and of W10000 and the subsequent extended link registers are accepted.
The RIRD instruction can set the arrival monitoring time and the number of resends in the following link
special registers (SW).
• RIRD/RIWT instruction: Arrival monitoring time (SW0009)
• RIRD/RIWT instruction: Number of resends (SW000B)
When "RIRD/RIWT instruction: Number of resends (SW000B)" is set, the time taken for the RIRD instruction
to be completed with an error is determined by the following.
(RIRD/RIWT instruction: Number of r 1)
RIRD/RIWT instruction: Arrival monitoring time
However, if the target station (relay source station when addressed to another network) has been
disconnected at the time of RIRD instruction execution, no retry is executed. If the RIRD instruction is
completed with an error, re-execute the RIRD instruction after the target station (relay source station when
addressed to another network) returns.
If an error (error code: E504H) occurs in CC-Link IE Controller Network, a retry cannot be performed. Wait
until the instruction completes with an error, and execute the RIRD instruction again.
Device category
Name
Date type
Unit
Access code
Attribute code
Bit
Word
Input relay
X
Hexadecimal
01H
05H
Output relay
Y
Hexadecimal
02H
05H
Internal relay
M
Decimal
03H
05H
Latch relay
L
Decimal
83H
05H
Link relay
B
Hexadecimal
23H
05H
Timer (contact)
T
Decimal
09H
05H
Timer (coil)
T
Decimal
0AH
05H
Timer (current value)
T
Decimal
0CH
05H
Retentive timer (contact)
ST
Decimal
89H
05H
Retentive timer (coil)
ST
Decimal
8AH
05H
Retentive timer (current value)
ST
Decimal
8CH
05H
Counter (contact)
C
Decimal
11H
05H
Counter (coil)
C
Decimal
12H
05H
Counter (current value)
C
Decimal
14H
05H
Data register
D
Decimal
04H
05H
Link register
W
Hexadecimal
24H
05H
File register
R
Decimal
84H
05H
Link special relay
SB
Hexadecimal
63H
05H
Link special register
SW
Hexadecimal
64H
05H
Special relay
SM
Decimal
43H
05H
Special register
SD
Decimal
44H
05H
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......