7 APPLICATION INSTRUCTIONS
7.8 String Processing Instructions
647
7
Processing details
• These instructions convert the digit in decimal notation of the 32-bit binary data in the device specified by (s) to the ASCII
code, and store the converted data in the device number specified by (d) and later.
• The format of the decimal ASCII data to be stored in (d) depends on the status of SM705 (Number of conversion digits
selection).
*1 For the firmware version of the CPU module supporting SM705, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
A CPU module which does not support SM705 operates in the same way as SM705 is off even if it is turned on.
■
Operation overview
The following figure shows the operation when SM705 (Number of conversion digits selection) is off and on.
Ex.
When the DBINDA(P) instruction is executed with a numeric value "-123456" stored in (s)
• When SM705 is off, the number of digits is fixed. The first character is a sign and it is 2DH(-) in the above example. (If (s) is
0 or positive, the first character is 20H (space).) The numeric part is right-justified. When the length of the numeric part is
less than 10 digits, the ASCII code 20H (space) is stored for the ASCII code of the upper digit(s).
• When SM705 is on, data is left-justified. When the length of the numeric part is less than 10 digits, 00H is stored in the end.
Status of SM705
Storage format of (d)
Reference
OFF
Data is stored in a fixed number of digits (a sign + 10 digits)
Page 648 Operation of when SM705 (Number of
conversion digits selection) is off
ON
Each digit is stored left-justified depending on the value of (s).
Page 649 Operation of when SM705 (Number of
conversion digits selection) is on
b31
b0
∙∙∙
(s)
DBINDA(P)
SM705: OFF
b15
b0
∙∙∙
20H
2DH
(d)+0
-
2
1
SP
SP
SP
20H
20H
(d)+1
31H
20H
(d)+2
33H
32H
(d)+3
35H
34H
(d)+4
00H
36H
(d)+5
35H
34H
(d)+2
00H
36H
(d)+3
(d)+4
(d)+5
4
3
6
5
SP
NULL
-
6
5
3
2
1
NULL
4
b15
b0
∙∙∙
31H
2DH
(d)+0
33H
32H
(d)+1
SM705: ON
-123456
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......