5 SEQUENCE INSTRUCTIONS
5.3 Output Instructions
Processing details
• This instruction turns off the annunciator specified by (d) when the execution command turns on.
• The annunciator number (F number) turned off is deleted from the special register (SD64 to SD79), and the value in SD63
is decremented by one.
• If the value in SD63 is 16, the corresponding annunciator number is deleted from SD64 to SD79 by the RST instruction. If
an annunciator with a number not registered in SD64 to SD79 has been turned on, the number is newly registered. If all
annunciator numbers in SD64 to SD79 are reset (turned off), the USER LED of the CPU module turns off.
Ex.
When the value in SD63 is 16 and there is an annunciator number that is not registered
Operation error
There is no operation error.
(1) Reset F90.
(2) The F number in SD66 is shifted to this area.
(3) New F number is stored.
SD63
SD64
SD65
SD66
SD78
SD79
SD63
SD64
SD65
SD77
SD78
SD79
16
233
90
700
145
1027
16
233
700
SD67
SD66
28
28
145
1027
(2)
(1)
(3)
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......