1606
18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.2 Writing Data to the Intelligent Device Station/Remote Device Station (16-bit Address Specified)
Setting data
■
Description, range, data type
*1 A channel is used only for the REMFR, REMTO, REMFRD, and REMTOD instructions.
The same channel number used for the link dedicated instructions (such as the READ instruction) can be set.
*2 This is the start I/O number (first three digits in four-digit hexadecimal representation) of intelligent function modules.
*3 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Use the REMTOD instruction if the start address of the buffer memory area (s4) exceeds FFFFH (65535).
■
Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
Operand
Description
Range
Data type
Data type (label)
(J)
JP.REMTO
Target network number
1 to 239
16-bit unsigned binary
ANY16
ZP.REMTO
Target network number
1 to 239
String
ANY16_OR_STRING
_SINGLE
(s1)
Channel of the own station, which is used for the
instruction
1 to 32
16-bit unsigned binary
ANY16
(s2)
Target station number
1 to 120
16-bit unsigned binary
ANY16
(s3)
Start I/O number of target station
■
Head module:
00H to FEH
■
Modules other than the head
module:
00H (fixed)
16-bit unsigned binary
ANY16
(s4)
Start address of the buffer memory area of the
intelligent device station or the remote device station
to which the data is written
0000H to FFFFH (0 to 65535)
16-bit unsigned binary
ANY16
(s5)
Start device of the own station, where the write-
target data is stored
Device name
ANY16
(n)
Number of write data points (in units of words)
1 to 240
16-bit unsigned binary
ANY16
(d)
Device of the own station, which turns on for one
scan upon completion of the instruction.
When the instruction completes with an error, (d)+1
also turns on.
Bit
ANYBIT_ARRAY
(Number of elements:
2)
EN
Execution condition
Bit
BOOL
ENO
Execution result
Bit
BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
(J)
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z LT, LST,
LC
LZ
K, H E $
(J)
JP.RE
MTO
ZP.RE
MTO
(s1)
(s2)
(s3)
(s4)
(s5)
(n)
(d)
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......