1398
11 PROCESS CONTROL INSTRUCTIONS
11.7 Auto Tuning
■
Timeout (after maximum ramp) determination processing
This function determines whether the auto tuning processing has reached the AT1 timeout time after maximum ramp
(AT1TOUT2).
However, if the timeout time (after maximum ramp) counter initialization completion flag is 0, "step manipulated value set
processing" is performed.
■
Step manipulated value set processing
This function checks the step manipulated value set completion flag to determine whether the step manipulated value has
been set (1) or not set (0).
• When the step manipulated value set completion flag is 0, the following processing is performed.
The AT1 step manipulated value (AT1SETPMV) is added to the manipulated value (MV).
T1=MV+AT1STEPMV
The upper/lower limiter function performs the following operations, and outputs the result to the output upper limit alarm (BB4)
and output lower limit alarm (BB5).
• When the step manipulated value set completion flag is 1, "sampling cycle determination processing" is performed.
■
Sampling cycle determination processing
This function checks the AT1 sampling period (AT1ST) to determine whether the sampling period has been reached.
• If the sampling period has not been reached, the S.AT1 instruction is terminated.
• If the sampling period has been reached, "response waveform observation processing" is performed.
Auto tuning processing
Processing details
If the AT1 timeout time after maximum ramp (AT1TOUT2) is
reached
"Identification processing" is performed.
If the AT1 timeout time after maximum ramp (AT1TOUT2) has
not been reached
"Step manipulated value set processing" is performed.
Condition
Result
BB4
BB5
BB16
MV
Processing after upper/lower limiter
T1 > MH
1
0
1
Original MV
remains
unchanged.
The S.AT1 instruction is terminated.
T1 < ML
0
1
1
ML
T1
MH
0
0
0
T1
The following processing is performed.
• The step manipulated value set completion flag is set to 1.
• The auto tuning counter is set to 0.
• The input value (E1) is stored in auto tuning start PV0.
• The input value (E1) is stored in the last measurement value (PV
n-1
).
• The maximum slope value, maximum ramp counter, maximum ramp PV, response
speed (R), and equivalent dead time (L) are set to 0.
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......