Slave station setting data
*1 Repeat this setting for the total number of connected modules/stations.
*2 If a local station is specified, specify the intelligent device station.
■
Reserved station specification data
*1 For two or more stations occupied, specify only the slave station start number.
Operand: (s2)
Device
Item
Description
Setting range
Set by
+0 to +63
Station information
settings
Specifies the station number, the number of occupied stations, and the station type
for each slave station.
The default value range is 0101H to 0140H, meaning that the station number is 1 to
64, the number of occupied stations is 1 station occupied, and the station type is
remote I/O station for Ver. 1.
User
(1) Station number setting
1 to 64
01H to 40H
User
(2) Number of occupied stations setting
• 1H: 1 station occupied
• 2H: 2 stations occupied
• 3H: 3 stations occupied
• 4H: 4 stations occupied
1H to 4H
User
(3) Station type setting
• 0H: Remote I/O station for Ver. 1
• 1H: Remote device station for Ver. 1
• 2H: Intelligent device station for Ver. 1
• 5H: Single remote device station for Ver. 2
• 6H: Single intelligent device station for Ver. 2
• 8H: Double remote device station for Ver. 2
• 9H: Double intelligent device station for Ver. 2
• BH: Quadruple remote device station for Ver. 2
• BH: Quadruple intelligent device station for Ver. 2
• EH: Octuple remote device station for Ver. 2
• FH: Quadruple intelligent device station for Ver. 2
0H to FH
User
Operand: (s3)
Device
Item
Description
Setting range
Set by
+0 to +3
Reserved station
specification
Specifies a reserved station in a station-by-station manner.
• 0: Not specified
• 1: Specified
The default value is "0: Not specified" for all stations.
User
b15
b12 b11
b8 b7
b0
(3)
(2)
(1)
…
…
…
b15
16
32
48
64
15
31
47
63
14
30
46
62
13
29
45
61
4
20
36
52
3
19
35
51
2
18
34
50
1
17
33
49
b14
b13
b12
b3
b2
b1
b0
(s3)+0
(s3)+1
(s3)+2
(s3)+3
…
…
…
…
…
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......