15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
+7
Number of resends
■
Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s1)+8.
• 0 to 15 (times)
■
At completion of instruction
The number of resends performed (result) is stored.
• 0 to 15 (times)
0 to 15
User/
system
+8
Arrival monitoring time
[CC-Link IE Controller Network or CC-Link IE Field Network]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
• 0: 10s
• 1 to 32767: 1 to 32767s
0 to 32767
User
[Ethernet]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
• 0 to (TCP resend timer value): The TCP resend timer value is assumed as the
monitoring time.
• (TCP resend timer value + 1) to 16383: (TCP resend timer value + 1) to 16383s
0 to 16383
User
+9
Request data length
Specify the number of request data (words).
(Number of words of data stored in the request data storage device (s2))
• Reading clock data: 2
• Writing clock data: 6
2, 6
User
+10
Response data length
The number of response data (words) is stored.
(Number of words of data stored in the response data storage device)
• Reading clock data: 6
• Writing clock data: 2
2, 6
System
+11
Clock setting flag
The validity status (valid or invalid) of the data in (s1)+12 and later is stored.
Note that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
• 0: Invalid
• 1: Valid
System
+12
Clock data
(Set only in an
abnormal state)
(No information is
stored if an error is
detected in the own
station.)
Upper 8 bits: Month (01H to 12H)
Lower 8 bits: Lower 2 digits of year (00H to 99H)
System
+13
Upper 8 bits: Hour (00H to 23H)
Lower 8 bits: Day (01H to 31H)
System
+14
Upper 8 bits: Second (00H to 59H)
Lower 8 bits: Minute (00H to 59H)
System
+15
Upper 8 bits: Year (00H to 99H: Upper two digits of the year)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
System
+16
Error detection network
number
The network number of the station in which an error was detected is stored. (No
information is stored if an error is detected in the own station.)
• 1 to 239 (Network number)
1 to 239
System
+17
Error-detected station
number
The station number of the station where an error was detected is stored. (No
information is stored if an error is detected in the own station.)
[Ethernet or CC-Link IE Controller Network]
• 1 to 120: Station number
[CC-Link IE Field Network]
• 125: Master station
• 1 to 120: Local station, intelligent device station, submaster station
1 to 120, 125
System
Operand: (s1)
Device
Item
Description
Setting range
Set by
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......