7 APPLICATION INSTRUCTIONS
7.28 Routing Information Instructions
1075
7
Processing details
• These instructions write the routing information stored in the device specified by (s2) and later to the area with the transfer
destination network number specified by (s1).
• The following figure shows the data stored in the device specified by (s2) and later.
• The specification ranges of relay station number are as follows.
• If the data of the transfer destination network number specified by (s1) has already been set in parameter, the data is
overwritten with the data stored in the device specified by (s2) and later.
• If the data in the device areas specified by (s2) to (s2)+2 are all 0, the data of the transfer destination network number
specified by (s1) is deleted from parameter.
Operation error
Start device
Item
Range
(s2)
Relay network number
1 to 239
(s2)+1
Relay station number
Refer to the following table.
(s2)+2
Dummy
Network type
Specification range
MELSECNET/H
1 to 64
CC-Link IE Controller Network
1 to 120
CC-Link IE Field Network (master station)
Fixed to 125
CC-Link IE Field Network (local station)
1 to 120
Error code
(SD0)
Description
3405H
The value set to (s1) is out of the range, 1 to 239.
Any of the data in the device areas specified by (s2) and later exceeds the following range.
• (s2)+0: 1 to 239
• (s2)+1: 1 to 120, 125
The total number of routing information registered in parameter of the network module and registered by using the RTWRITE instruction
exceeds 238.
A transfer destination network number which is not registered in parameter is specified as a deletion target.
A zero is specified in only either of the device areas specified by (s2) and (s2)+1.
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......