446
6 BASIC INSTRUCTIONS
6.6 Data Conversion Instructions
Processing details
• These instructions convert the hexadecimal ASCII data stored in the device areas specified by (s) and later to 16-bit binary
data, and store the converted data in the device specified by (d).
• The setting method of the hexadecimal ASCII data to be set in (s) depends on the status of SM705 (Number of conversion
digits selection).
*1 For the firmware version of the CPU module supporting SM705, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Application)
A CPU module which does not support SM705 operates in the same way as SM705 is off even if it is turned on.
■
Setting method of (s) for when SM705 (Number of conversion digits selection) is off
• Set hexadecimal ASCII data with 4 digits (fixed) in (s) to (s)+1.
• The ASCII data in the device specified by (s) to (s)+1 is within the range from 0000H to FFFFH.
• The data of (s)+2 or later is ignored.
• A value from 30H to 39H and 41H to 46H can be set in each place of ASCII code.
Ex.
When 5A8DH is specified in (s)
■
Setting method of (s) for when SM705 (Number of conversion digits selection) is on
Set hexadecimal ASCII data with a desired number of digits (including 00H (NULL code)) in (s). Note that 00H (NULL code) is
not required to be set for the maximum number of digits (4 digits).
The following table lists the setting method of (s).
• The ASCII data in the device specified by (s) to (s)+1 is within the range from 0000H to FFFFH.
• The data of (s)+2 or later is ignored.
• A value from 30H to 39H and 41H to 46H can be set in each place of ASCII code.
• If a value 00H is set in each place of ASCII code, the value will be processed as the end of the hexadecimal ASCII data.
Status of SM705
Setting method of (s)
Reference
OFF
Set (s) with a fixed number of digits (4 digits).
Page 446 Setting method of (s) for when SM705 (Number of
conversion digits selection) is off
ON
Set (s) with a desired number of digits (maximum: 4 digits).
Page 446 Setting method of (s) for when SM705 (Number of
conversion digits selection) is on
ASCII
: ASCII code (
th digit)
Value to be set
in (s)
Data of (s) to (s)+1
Value to be set
in (s)
Data of (s) to (s)+1
• 0H to FH
• Set 00H in the upper byte of (s)+0.
• The data of (s)+1 or later is ignored.
• 10H to FFH
• Set 00H in the lower byte of (s)+1.
• The data of the upper byte of (s)+1 or later is ignored.
• 100H to FFFH
• Set 00H in the upper byte of (s)+1.
• The data of (s)+2 or later is ignored.
• 1000H to FFFFH
• The data of (s)+2 or later is ignored.
ASCII
: ASCII code (
th digit)
(s)
(s)+1
b15
b0
∙∙∙
∙∙∙
b7
b8
b0
∙∙∙
b15
(d)
ASCII 3
ASCII 1
ASCII 4
ASCII 2
BIN16
(s)
(s)+1
b15
b0
∙∙∙
∙∙∙
b7
b8
b0
∙∙∙
b15
(d)
41H (A)
44H (D)
35H (5)
38H (8)
5A8DH
(s)+1
(s)
b15
b0
∙∙∙
∙∙∙
b7
b8
00H
ASCII 1
(s)+1
(s)
b15
b0
∙∙∙
∙∙∙
b7
b8
ASCII 1
00H
ASCII 2
(s)+1
(s)
b15
b0
∙∙∙
∙∙∙
b7
b8
ASCII 2
00H
ASCII 3
ASCII 1
(s)+1
(s)
b15
b0
∙∙∙
∙∙∙
b7
b8
ASCII 3
ASCII 1
ASCII 4
ASCII 2
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......