1598
17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
17.5 Setting the Station Number to Own Station
■
Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
■
Control data
• The UINI instruction can be executed only once.
• If the UINI instruction is issued after the station number has been determined, it will complete with an error.
• If the UINI instruction completes with an error before the station number is determined, take corrective
action to correct the error content before retrying to execute the instruction.
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
(U)
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD,
R, ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H E
$
(U)
G(P).UINI
Z(P).UINI
(s)
(d)
Operand: (s)
Device
Item
Description
Setting range
Set by
+0
Not used
+1
Completion status
The instruction completion status is stored.
• 0: Normal
• Other than 0: Error (error code)
System
+2
Change target
specification
0001H (fixed)
0001H
User
+3
Station number of own
station
Specifies the station number to be set.
1 to 120
User
+4 to +9
Not used
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......