18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.6 Reading the Module Status Information of an Intelligent Device Station
1627
18
: Supported,
: Not supported
*2
Device
Bit
Item
Description
Power
supply
module
Base
unit
Modules
mounted on the
CPU slot and
slot No.0 to
No.63
1st word
b0 to b3
Reserved
Fixed to 0
b4 to b7
Module type
0000:Input module, or not set (default)
0010:Output module
0100:I/O combined module (different numbers)
0110:I/O combined module (same number)
1000:Intelligent function module
Further details can be checked in b0 to b3 of the 3rd
word.
b8 to b10
Series
000:
(default)
010:MELSEC-Q series module
011:MELSEC iQ-R series module
111:Unknown
b11 to b15
Reserved
Fixed to 0
2nd word
b0 to b1
Error status
00: No error (default)
01: Minor error
10: Moderate error
11: Major error
b2
Module ready
status
0: Not ready (default)
1: Ready
b3 to b5
Reserved
Fixed to 0
b6 to b7
Inter-module
synchronization
00: Not synchronized (default)
01: Preparing for synchronization
10: Synchronized
11: Synchronization error
b8 to b9
Reserved
Fixed to 0
b10
External power
supply
0: Normal operation (default)
1: Power off
b11
Fuse
0: Normal operation (default)
1: Fuse blown
b12
Reserved
Fixed to 0
b13
Online module
change
0: Not being performed (default)
1: Module being changed online
b14
Reserved
Fixed to 0
b15
Module access
0: Disabled (default)
1: Enabled
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......