18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.7 Setting Parameters
*1 If a value outside the setting range is set for the appropriate station information setting, the instruction will complete with an error.
*2 The specified number of points is regarded as the number of RX/RY or RWr/RWw points.
Repeat this setting for the total number of slave stations that was set in the control data.
■
Reserved station setting data (for master station setting only)
*1 Make the setting for the station number that was set with the appropriate setting information setting data.
If the specified total number of slave stations does not match the individual station setting data, the total
number of individual stations specified in the total number of slave stations take precedence. Individual station
information which is specified exceeding the total number of slave stations is ignored. Note that 1 is added to
the total number of slave stations when the submaster function enabled/disabled ((s1)+1 bit 3) is enabled (1).
+595
For 120th
module
Slave station
setting
information
Sets the station type.
Same as
(s2)+0
User
+596
RX/RY offset
Sets the offset value from the head of RX/RY (in units of 16 points).
0 to 16368
User
+597
Number of RX/
RY points
Sets the number of RX/RY points.
• If the station type is master or local: 0 to 2048 points
• If the station type is intelligent device: 0 to 2048 points (in units of 16 points)
• If the station type is remote I/O: 0 to 64 points (in units of 16 points)
• If the station type is remote device: 0 to 128 points (in units of 16 points)
0 to 2048
0 to 64
0 to 128
User
+598
RWr/RWw
offset
Sets the offset value from the start of RWr/RWw (in units of 4 points).
0 to 8188
User
+599
Number of RWr/
RWw points
Sets the number of RWr/RWw points.
• If the station type is master or local: 0 to 256 points (in units of 16 points)
• If the station type is intelligent device: 0 to 1024 points (in units of 4 points)
• If the station type is remote device: 0 to 64 points (in units of 4 points)
0 to 256
0 to 1024
0 to 64
User
+600 to
+604
For 121st
module
Same as above
User
Operand: (s3)
Device
Item
Description
Setting range
Set by
+0 to +7
Station 1 to 120
specification
Specify the reserved station.
• 0: Not specified
• 1: Specified
Each number in the table indicates a station number.
The default parameter specifies that all stations are 0 (not specified).
Left
User
Operand: (s2)
Device
Item
Description
Setting
range
*1
Set by
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
(s3)+0
(s3)+1
(s3)+2
(s3)+3
(s3)+4
(s3)+5
(s3)+6
(s3)+7
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......