21 A/D CONVERSION INSTRUCTIONS
21.2 Reading the User Range Setting Values
1729
21
• For R60DA4, R60DAH4
Set only the save data type setting (s)+2. A data write to an area to be set by the system does not result in a normal read of
the offset/gain setting values.
Operand: (s)
Device
Item
Description
Setting range
Set by
+0
System area
+1
Completion status
The instruction completion status is stored.
• 0: Completed successfully
• Other than 0: Completed with an error (error code)
System
+2
Save data type setting
Specify the user range setting for reading offset/gain setting
values.
• 0: User range setting (voltage specification)
• 1: User range setting (current specification)
0000H to 000FH
User
+3
System area
+4
CH1 Factory default setting offset value
System
+5
CH1 Factory default setting gain value
System
+6
CH2 Factory default setting offset value
System
+7
CH2 Factory default setting gain value
System
+8
CH3 Factory default setting offset value
System
+9
CH3 Factory default setting gain value
System
+10
CH4 Factory default setting offset value
System
+11
CH4 Factory default setting gain value
System
+12
CH1 User range setting offset value
System
+13
CH1 User range setting gain value
System
+14
CH2 User range setting offset value
System
+15
CH2 User range setting gain value
System
+16
CH3 User range setting offset value
System
+17
CH3 User range setting gain value
System
+18
CH4 User range setting offset value
System
+19
CH4 User range setting gain value
System
b15
b3
b2
b1
b0
0
…
CH4 CH3 CH2 CH1
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......