6 BASIC INSTRUCTIONS
6.6 Data Conversion Instructions
479
6
Processing details
• These instructions separate the lower (n) nibble(s) (4 bits/nibble) from the 16-bit binary data in the device specified by (s),
and store each of the separated data in the lower 4 bits of the (n) points of data in the device specified by (d).
• The upper 12 bits of the (n) points of data in the device specified by (d) are filled with 0s.
• Specify a value 1 to 4 for (n).
• When (n)=0, no processing is performed and the (n) points of data starting from the device specified by (d) remain
unchanged.
Operation error
(1) Data storage area
(2) Filled with 0s.
Error code
(SD0)
Description
3401H
The value specified by (n) is out of the range, 0 to 4.
∙∙∙
∙∙∙
b3
b0
∙∙∙
b7
b4
∙∙∙
b11
b8
∙∙∙
b15 b12
b0
b3
∙∙∙
b4
b15
(s)
(d)
(d)+1
(d)+2
(d)+3
(n)
(2)
(1)