11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1315
11
■
Block memory
■
Operation constant
■
Execution cycle (
T)
Set the execution cycle (
T) in SD816 and SD817 in single-precision real number.
Processing details
This instruction holds the last value and outputs it when the variation rate of input (E1) exceeds the limit.
E1: Input value, BW: Output value
The S.VLMT2 instruction performs the following operations.
Operand: (d1)
Device
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
BW
Output value
-999999 to 999999 [%]
Single-precision
real number
System
+2
BB
BB1
Positive
direction limit
alarm
0: No alarm
1: Alarm
16-bit unsigned
binary
System
BB2
Negative
direction limit
alarm
Operand: (s2)
Device
Symbol
Name
Recommended range
Data type
Standard
value
Set by
+0
+1
V1
Positive
direction limit
value
0 to 999999 [%/s]
Single-precision
real number
100.0
User
+2
+3
V2
Negative
direction limit
value
0 to 999999 [%/s]
Single-precision
real number
100.0
User
+4
+5
HS1
Positive
direction
hysteresis
0 to 999999 [%]
Single-precision
real number
0.0
User
+6
+7
HS2
Negative
direction
hysteresis
0 to 999999 [%]
Single-precision
real number
0.0
User
Condition
Input (E1-BW)
BW
BB1
BB2
Positive direction E1
BW
(E1-BW)
(V1
T)
BW=BW
1
0
(E1-BW) < (V1
T-HS1)
BW=E1
0
0
Others
BW=BW
Last value
Last value
Negative direction E1<BW
(BW-E1)
(V2
T)
BW=BW
0
1
(BW-E1)<(V2
T-HS2)
BW=E1
0
0
Others
BW=BW
Last value
Last value
b15
b1 b0
...
BB1
BB2
BB1
BB2
E1 (BW)
E1
BW
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......