1 OVERVIEW
1.2 Data Specification Method
Bit data
Data size and data range
Bit data is handled in increments of bits such as contacts and coils.
Handling bit data with bit devices and labels
Bit data of one point per point can be handled.
Handling bit data with bit word devices
By specifying a bit number for a word device, bit data of the specified bit number can be handled.
A bit in a word device can be specified by "Word device number.Bit number".
A bit number can be specified in hexadecimal in the range from 0 to F.
For example, bit 5 (b5) of D0 is specified as D0.5, and bit 10 (b10) of D0 is specified as D0.A.
The following word devices support bit specification.
A bit number of a safety device used in safety programs executed by the Safety CPU can be specified in hexadecimal within
the range from 0 to F.
For example, bit 5 (b5) of SA\D0 is specified as SA\D0.5, and bit 10 (b10) of SA\D0 is specified as SA\D0.A.
The following word devices support bit specification.
Data name
Data size
Value range
Bit data
1 bit
0, 1
Item
Device
Word devices which support bit specification
• Data register (D)
• Link register (W, J
\W)
• Link special register (SW, J
\SW)
• Function register (FD)
• Special register (SD)
• Module access device (U
\G)
• CPU buffer memory access device (U3E
\G, U3E
\HG)
• File register (R, ZR)
• Module refresh register (RD)
Item
Device
Word devices which support bit specification
• Safety data register (SA\D)
• Safety link register (SA\W)
• Safety special register (SA\SD)
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......