6 BASIC INSTRUCTIONS
6.6 Data Conversion Instructions
435
6
Processing details
• These instructions convert the (n) points of 16-bit binary data (0 to 9999) starting from the device specified by (s) to BCD
data, and store the converted data in the device specified by (d) and later.
Operation error
(1) Set 0s.
Error code
(SD0)
Description
2821H
The device ranges specified by (s) and (d) are overlapping.
3401H
The (n) points of data starting from the device specified by (s) is out of the range, 0 to 9999.
(s)
(s)+1
(s)+2
(s)+(n)-2
(s)+(n)-1
(d)
(d)+1
(d)+2
(d)+(n)-2
(d)+(n)-1
BCD 5555
BCD 4321
BCD 1545
BCD 5678
BCD 1234
BIN 1234
BIN 5678
BIN 1545
BIN 4321
BIN 5555
∙∙∙
∙∙∙
∙∙∙
∙∙∙
∙∙∙
∙∙∙
(n)
(n)
0 0 0 1 0 1 0 1 1 0 1 1 0 0 1 1
0 0 0 1 0 0 0 0 1 1 1 0 0 0 0 1
0 0 0 0 0 1 1 0 0 0 0 0 1 0 0 1
0 0 0 1 0 1 1 0 0 0 1 0 1 1 1 0
0 0 0 0 0 1 0 0 1 1 0 1 0 0 1 0
0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1
0 0 0 1 0 1 0 1 0 1 0 0 0 1 0 1
0 1 0 1 0 1 1 0 0 1 1 1 1 0 0 0
0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0
8000
4000
2000
1000
800
400
200
100
80
40
20
10
8
4
2
1
8192
4096
2048
1024
512
256
128
64
32
16
8
4
2
1
(1)
BCD
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......