1 OVERVIEW
1.5 Precautions on Programming
61
1
If PLS instructions of the same device are used
The PLS instruction turns on the specified device when the execution command specifies an off-to-on change. The specified
device is turned off unless the execution command specifies an off-to-on change (i.e. off to off, on to on, on to off).
Thus, if two or more PLS instructions of the same device are issued during one scan, the specified device is turned on when
the execution command of each PLS instruction specifies an off-to-on change. The specified device is turned off unless the
execution command specifies an off-to-on change.
Thus, if two or more PLS instructions are issued during one scan, the device turned on by a PLS instruction may not turn on
for one scan.
• If X0 and X1 differs in the on/off timing (i.e. the specified device does not turn on for one scan)
(1) Since X0 turns on, M0 turns on.
(2) Since X1 is other than turning on, M0 turns off.
(3) Since X0 is other than turning on, M0 remains off.
(4) Since X1 turns on, M0 turns on.
PLS
M0
PLS
X1
X0
M0
ON
ON
X1
X0
PLS M0
PLS M0
PLS M0
X1
X0
PLS
ON
OFF
OFF
OFF
M0
X1
X0
END
END
END
ON
(1)
(2)
(3)
(4)
OFF
OFF
M0
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...