10 PID CONTROL INSTRUCTIONS
10.3 PID Control Instructions (Exact Differential)
• Write data to the I/O data "Write" area by users with the program. Users can read data from the I/O data "Read" area with
the program. Never attempt to write data to the area indicated by "Read/write disabled" or "Read"; otherwise, normal
operation can no longer be performed. Note that, when starting control from the initial status, the data areas must be
cleared by the program.
• Even when the manual manipulated value (MV
MAN
) is output in manual mode, execute the PIDCONT(P) instruction every
scan. Unless the PIDCONT(P) instruction is executed, the bumpless function cannot be performed.
• Apply an interlock using the READY signal of each module so that the PIDCONT(P) instruction is executed only when the
A/D converter module used to obtain the process value (PV) and the D/A converter module used to output the manipulated
value (MV) are normal. If the instruction is executed when these modules are not normal, PID operation cannot be
performed normally as the result of failure in normal acquisition of process values (PV) or in normal output of manipulated
values (MV).
Operation error
(1) Control command
(2) READY signal of the A/D converter module
(3) READY signal of the D/A converter module
Error code
(SD0)
Description
3405H
The value of the data set in the I/O data area specified by (s) is out of the setting range.
3422H
The PIDINIT(P) instruction is not executed before the PIDCONT(P) instruction.
PIDCONT
D100
(1)
(2)
(3)
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......