17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
17.1 Remote RUN
*1 If the instruction is executed with group or all stations specification:
For the target station CPU type, specify either 0000H or 03FFH. If the target station is in CC-Link IE Field Network, group specification is
not available. To check that the data has been written successfully in the target station, examine whether the CPU module of the
destination has entered the RUN state.
*2 If the instruction is executed with the control system CPU (03D0H) or standby system CPU (03D1H) specified, it may complete with an
error if system switching occurs in the target station (error code: 4244H, 4248H).
Retry to execute the instruction if it completed with an error due to the above error.
• Remote RUN is enabled when the RUN/STOP/RESET switch of the target station CPU module is "RUN."
• If the target station CPU module is system protected, remote RUN will fail.
• If the target station CPU module has already been remotely stopped or paused from another station, RUN
will fail if (s4) is "Not forcibly executed (0001H)."
■
Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
Processing details
• Remote RUN is executed for the target station CPU module according to the (s4) specification details. The target station is
specified with the target network number (J) or the start I/O number (U) of the own station or node and the target station
number (s2). After completion of request to the target station, the completion device specified by (d) turns on.
• The specifiable stations are those with the specified network number that are included in one of the following networks.
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B,
SB, FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD,
R, ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H
E
$
J
U
(J/U)
J(P).RRUN
G(P).RRUN
Z(P).RRUN
(s1)
(s2)
(s3)
(s4)
(d)
CH: Channel
• MELSECNET/H
• MELSECNET/10
• CC-Link IE Controller Network
• CC-Link IE Field Network
• Ethernet
(s4)
RUN
RRUN
CH8
CHn
CH1
CC-Link IE Controller
Network module
CPU module
CPU module
Network module
[Own station]
[Target station]
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......