19 CC-LINK INSTRUCTIONS
19.4 Writing Data to the Buffer Memory of the Specified Intelligent Device Station
1655
19
■
Applicable devices
*1 Index modification is not available.
*2 FX and FY cannot be used.
*3 FD cannot be used.
*4 T, ST, C, and FD cannot be used.
■
Control data
*1 Specify a value within the capacity of the target station buffer memory area.
■
Interlock signal
*1 For the interlock signal, refer to the following.
Manual of the intelligent device station from which to read data
*2 The error code stored in the error code storage device is the same as the completion status of control data ((s1)+0).
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
(U)
X, Y, M, L,
SM, F, B, SB,
FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H E
$
(U)
(s1)
(s2)
(s3)
(d)
Operand: (s1)
Device
Item
Description
Setting range
Set by
+0
Completion status
The completion status is stored upon completion of the instruction.
• 0: Completed successfully
• Other than 0: Completed with an error (error code)
System
+1
Station number
Specify the station number of the target station.
1 to 64
User
+2
Access/attribute code
Specifies 0004H.
0004H
User
+3
Buffer memory address
Specifies the start address of the buffer memory area to which to write data.
Refer to the
manual of the
target station.
User
+4
Number of write points
Specifies, in units of words, the number of points to be written.
1 to 480
User
Operand: (s3)
Device
Item
Description
Setting
range
Set by
+0
RY: Specifies the number of the write request signal (RY) to be used for
interlock.
00H to 7FH
User
+1
RY: Specifies the number of the write completion signal (RY) to be used for
interlock.
00H to 7FH
User
RWr: Specifies the number of the device in which to store the error code
(RWr). If the error code storage device does not exist, specify FFH.
00H to 0FH,
FFH
User
+2
Completion mode
Specifies how the completion signal behaves.
• 0: Using Device 1
During completion, the RX signal specified by (s2)+1 turns on.
• 1: Using Device 2
For normal completion, the RX signal specified by (s2)+1 turns on. For error
completion, both RX and RX+1 turn on simultaneously.
0, 1
User
0
RY
b15
b8 b7
b0
…
…
RWr
*1
RX
b15
b8 b7
b0
…
…
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......