15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
1481
15
+8
Arrival monitoring time
[CC-Link IE Controller Network or CC-Link IE Field Network]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
■
When "0" is specified in bit 8 of (s1)+0
• 0: 10s
• 1 to 32767: 1 to 32767s
■
When "1" is specified in bit 8 of (s1)+0
• 0: 10s
• 1 to 65535: 1 to 65535
100ms
0 to 65535
User
[Ethernet]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
■
When "0" is specified in bit 8 of (s1)+0
Specify the TCP resend timer value or greater for the monitoring time till completion
of processing.
• 0 to (TCP resend timer value): The TCP resend timer value is assumed as the
monitoring time.
• (TCP resend timer value + 1) to 16383: (TCP resend timer value + 1) to 16383s
■
When "1" is specified in bit 8 of (s1)+0
• 0: 10s
• 1 to 65535: 1 to 65535
100ms
0 to 65535
User
+9
Write data length
Specify the number of words to be written.
■
Writing to RCPU, QCPU, or LCPU
• Channels 1 to 8 are used: 1 to 960 (words)
• Channels 9 and 10 are used: 1 to 8192 (words)
■
Writing to QnACPU
• 1 to 480 (words)
1 to 8192
User
+10
Not used
+11
Clock setting flag
The validity status (valid or invalid) of the data in (s1)+12 and later is stored. Note
that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
• 0: Invalid
• 1: Valid
System
+12
Clock data
(Set only in an
abnormal state)
Upper 8 bits: Month (01H to 12H)
Lower 8 bits: Lower 2 digits of year (00H to 99H)
System
+13
Upper 8 bits: Hour (00H to 23H)
Lower 8 bits: Day (01H to 31H)
System
+14
Upper 8 bits: Second (00H to 59H)
Lower 8 bits: Minute (00H to 59H)
System
+15
Upper 8 bits: Year (00H to 99H: Upper two digits of the year)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
System
+16
Error detection network
number
The network number of the station in which an error was detected is stored. (No
information is stored if an error is detected in the own station.)
• 1 to 239 (Network number)
1 to 239
System
+17
Error-detected station
number
The station number of the station where an error was detected is stored. (No
information is stored if an error is detected in the own station.)
[Ethernet or CC-Link IE Controller Network]
• 1 to 120: Station number
[CC-Link IE Field Network]
• 125: Master station
• 1 to 120: Local station, intelligent device station, submaster station
1 to 120,
125
System
Operand: (s1)
Device
Item
Description
Setting range
Set by
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......