17 CC-LINK IE CONTROLLER NETWORK INSTRUCTIONS
17.3 Reading Clock Data from the Programmable Controller on Another Station
1587
17
Setting data
■
Description, range, data type
*1 If the instruction is executed with the control system CPU (03D0H) or standby system CPU (03D1H) specified, it may complete with an
error if system switching occurs in the target station (error code: 4244H, 4248H).
Retry to execute the instruction if it completed with an error due to the above error.
■
Applicable devices
*1 FX and FY cannot be used.
*2 FD cannot be used.
*3 T, ST, C, and FD cannot be used.
Operand
Description
Range
Data type
Data type (label)
(J/U)
J(P).RTMRD
(J): Target station network number
1 to 239
16-bit unsigned binary
ANY16
G(P).RTMRD
(U): Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own node
00H to FEH
16-bit unsigned binary
ANY16
Z(P).RTMRD
(J): Target station network number
1 to 239
String
ANY16_OR_STRING_
SINGLE
Z(P).RTMRD
(U): Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own node
00H to FEH
String
ANY16_OR_STRING_
SINGLE
(s1)
Own station channel (
1 to 8, 11 to 18
16-bit unsigned binary
ANY16
(s2)
Target station number
1 to 120
16-bit unsigned binary
ANY16
(s3)
Specify that CPU module in the target station that is to be
accessed.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
0000H
03D0H to 03D3H
03E0H to 03E3H
03FFH
16-bit unsigned binary
ANY16
(d1)
Own station start device for storing the read clock data.
Device name
ANY16_ARRAY
(Number of elements: 4)
(d2)
Device of the own station, which turns on for one scan upon
completion of the instruction.
When the instruction completes with an error, (d2)+1 also
turns on.
Bit
ANYBIT_ARRAY
(Number of elements: 2)
EN
Execution condition
Bit
BOOL
ENO
Execution result
Bit
BOOL
Operand
Bit
Word
Double word Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B,
SB, FX, FY
J
\
T, ST, C, D, W,
SD, SW, FD,
R, ZR, RD
U
\G
, J
\
,
U3E
\(H)G
Z
LT, LST,
LC
LZ
K, H E
$
J
U
(J/U)
J(P).RTMRD
G(P).RTMRD
Z(P).RTMRD
(s1)
(s2)
(s3)
(d1)
(d2)
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......