16 ETHERNET INSTRUCTIONS
16.1 Open/Close Processing Instructions
*1 When the execution type is set to 0, the device areas in (s2)+4 to (s2)+14 are used by the system and the user must not use the areas.
*2 This item can be set when the connection number in (s1) is one from 1 to 7 and 9 to 15.
*3 This specification is enabled when UDP/IP is specified for the communication method (protocol).
Data cannot be sent through the connection for which 65535 (FFFFH) is specified. Specify a value from 1 to 65534 to send data.
*4 This specification is enabled when TCP/IP is specified for the communication method (protocol).
*5 This specification is enabled when UDP/IP is specified for the communication method (protocol).
*6 Settings are ignored if the open method (bits 10 and 11) specified by (s2)+4 is "10: Unpassive open".
Processing details
The GP.CONOPEN instruction is used for socket communications or fixed buffer communications.
For the combinations of available settings for connection opening, refer to the following.
MELSEC iQ-R Ethernet User's Manual (Application)
Operation error
The following figure shows an IP address setting example.
Example: IP address "10.97.24.200 (0A.61.18.C8)"
[Program example]
or
[Execution result]
(1) The data is stored from the lower byte.
+5
Own node port number
Specify the port number of the own node.
(Port numbers 5000 to 5009 is reserved for the system and cannot be used.)
1024 to 4999
5010 to 65534
(0400H to 1387H,
1392H to FFFEH)
User
+6
+7
IP address of external
device
Specify the IP address (IPv4) of an external device.
• The IP address is stored in (s2)+6 and (s2)+7.
• To enable broadcast, store FFFFFFFFH.
00000001H to
FFFFFFFFH
User
+8 to +13
System area
+14
Destination port
number
Specify the destination port number.
When receiving data from all port numbers, store FFFFH.
1024 to 65535
(0400H to FFFFH)
User
Error code
((s2)+1)
Description
C000H to CFFFH
MELSEC iQ-R Ethernet User's Manual (Application)
Operand: (s2)
Device
Item
Description
Setting range
Set by
MOV
H18C8
D206
MOV
H0A61
D207
[Program example]
DMOV
H0A6118C8
D206
D206
D207
18C8H
0A. 61. 18. C8
0A61H
(1)
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......