21 A/D CONVERSION INSTRUCTIONS
21.3 Restoring the User Range Setting Values
• Program example
Precautions
In the following cases, execution of the G(P).OGSTOR instruction results in an error.
• The module has been set as a target of synchronization.
• The simultaneous conversion mode has been selected on the high speed analog-digital converter module.
• The wave output mode has been selected on the D/A converter module.
In the following case, execution of the G(P).OGSTOR instruction will be disabled.
• The high-speed output mode has been selected on the high speed digital-analog converter module.
Operation error
(14) Set control data.
(31) Restore the offset/gain settings.
Error code
((s)+1)
Description
1860H
In the following cases, the G(P).OGSTOR instruction will be being executed.
• During offset/gain setting module
• Has been set as a target of module-to-module synchronization.
• During simultaneous conversion mode (R60ADH4)
• During wave output mode (D/A converter module)
1861H
The G(P).OGSTOR instruction is being executed consecutively.
1862H
The G(P).OGSTOR instruction is being executed for a model different from that for which the G(P).OGLOAD instruction has been
executed.
The G(P).OGSTOR instruction is being executed before the G(P).OGLOAD instruction is executed.
1863H
The value set in the save data type setting 1 (S)+2 or the save data type setting 2 (s)+3 is out of the valid range.
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......