11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1335
11
Processing details
This instruction provides control output according to the SV and MV patterns.
The S.PGS instruction has the following three output types.
The following is the processing block diagram of the S.PGS instruction. (The numbers (1) to (5) in the diagram indicate the
order of the processing.)
Output type
Description
Hold type
Outputs data while holding the value of setting time 10 (SV10).
Return type
Sets the set value (SV) to 0 and outputs the last value of the manipulated value (MV).
Cyclic type
Processes based on the setting time 1 (SV1) to 10 (SV10) and then restarts processing from setting time 1 (SV1).
MV
PGS
MV
5
, MV
6
MV
3
, MV
4
MV
7
, MV
8
MV
1
, MV
2
MV
9
, MV
10
SV
1
SV
2
SV
3
SV
4
SV
5
SV
6
SV
7
SV
8
SV
9
SV
10
SV
BW
MHA
SPA
PTNO
OR
MODE
MLA
BB1
(3)
(4)
(2)
(2)
BB2
BB3
(5)
MAN
MV, MV1 to MV16
SV, SV1 to SV16
ML, MH
MV
PGS
TYPE
SV count-up
MV
PGS
operation
Loop stop
determination
Loop stop
processing
OFF (all bits)
OFF (all bits)
BW=Last value
RUN (SPA=0)
STOP (SPA=1)
Output
Summary of Contents for MELSEC iQ-R Series
Page 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Page 34: ...32 MEMO ...
Page 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Page 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Page 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Page 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Page 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Page 2109: ......