194
5 SEQUENCE INSTRUCTIONS
5.3 Output Instructions
Processing details
• This instruction turns on the annunciator specified by (d) when the execution command turns on.
• When the annunciator (F) is turned on, the following are performed.
• If the value in SD63 is 16 (meaning 16 annunciators are already on), the annunciator number will not be stored in the
special register (SD64 to SD79) even when a new annunciator turns on.
Operation error
There is no operation error.
• The USER LED turns on.
• The annunciator number (F number) turned on is stored in the special register (SD64 to SD79).
• The value in SD63 is incremented by one.
(1) The data remain the same.
SD63
SD64
SD65
SD66
SD78
SD79
SD63
SD64
SD65
SD66
SD78
SD79
16
233
90
700
145
1027
16
233
90
700
145
1027
(1)
F30 ON