186
────────────────────────────────────────────────────
:SCALe [channel no.] :PT
────────────────────────────────────────────────────
Syntax
:SCALe
[1 - 6]
:PT
<NR2>
<NR2> = 0.0001 to 10000
Example
:SCALE1:PT 1000
Sets the PT ratio for channel 1 to
1000.
Syntax
:SCALe
[1 - 6]
:PT?
Response
syntax
:SCALE
[1-6]
:PT
<NR2>
Example
Transmission
Response
:SCALE1:PT?
:SCALE1:PT 1000
Syntax
:SCALe
[1 - 6]
:SC
<NR2>
<NR2> = 0.0001 to 10000
Example
:SCALE1:SC 1000
Sets the SC ratio for channel 1 to
1000.
Function
Sets the PT ratio for the specified input
unit.
Notes
・
Specifying a value which cannot be
selected because of the number of input
units installed results in an execution
error.
・
In 1P3W mode or above, for the channel
specification, enter the number of the
lowest-numbered channel in the
combination. For example, when using
input unit channels 1 to 3 in 3V3A
mode, specify "1". The channels in
combination can not be set individually.
・
Unless the :SCALe[channel no.]
:CONTrol command is set to ON, this
setting is invalid even if the PT ratio is
set.
Function
Queries the current setting of PT ratio for
the specified input unit.
Function
Sets the SC ratio for the specified input
unit.
Notes
・
Specifying a value which cannot be
selected because of the number of input
units installed results in an execution
error.
・
In 1P3W mode or above, for the channel
specification, enter the number of the
lowest-numbered channel in the
combination. For example, when using
input unit channels 1 to 3 in 3V3A
mode, specify "1". The channels in
combination can not be set individually.
・
Unless the :SCALe[channel no.]
:CONTrol command is set to ON, this
setting is invalid even if the SC ratio is
set.
:SCALe [
channel no.
] :PT
Sets the PT ratio.
:SCALe [
channel no.
] :PT?
Queries the PT ratio.
:SCALe [
channel no.
] :SC
Sets the SC ratio.
Summary of Contents for Power HiTester 3193
Page 2: ......
Page 50: ...32 3 9 Operations During Power Failure ...
Page 76: ...58 4 13 Degaussing ...
Page 80: ...62 5 2 Setting the Frequency Range fa ...
Page 108: ...90 9 3 Internal Circuit for the External Control and Timing ...
Page 112: ...94 10 3 Output Rate ...
Page 250: ...232 13 9 Error and Overflow Displays ...
Page 278: ...260 17 5 Internal Block Diagram ...
Page 284: ...266 19 2 Installation Procedures For JIS standard For EIA standard External Dimensions ...
Page 300: ...282 20 4 Internal Block Diagram of the 3193 ...
Page 306: ...INDEX 4 Index ...
Page 307: ......
Page 308: ......
Page 309: ......
Page 310: ......