Chapter 6 Control Modes of Operation
6-26
Revision June 2010
vibration of mechanical system. If P2-45 is set to 0, this parameter is disabled.
P2 - 46
DPH3
Notch Filter Attenuation Rate 3
(Resonance Suppression)
Communication Addr.:
025CH, 025DH
Default: 0
Related Section:
Applicable Control Mode: ALL
Section 6.3.7
Unit: dB
Range: 0 ~ 32
Data Size: 16-bit
Display Format: DEC
Settings:
This parameter is used to set magnitude of the resonance suppression that is set
by parameter P2-45. If P2-46 is set to 0, the parameters P2-45 and P2-46 are both
disabled.
P2 - 25
NLP
Low-pass Filter Time Constant
(Resonance Suppression)
Communication Addr.:
0232H, 0233H
Default: 2 (1kW and below models) or
Related Section:
5 (above 1kW models)
Section 6.3.7
Applicable Control Mode: ALL
Unit: 0.1ms
Range: 0 ~ 1000
Data Size: 16-bit
Display Format: DEC
Settings:
This parameter is used to set low-pass filter time constant of resonance
suppression. If P2-25 is set to 0, this parameter is disabled.
Summary of Contents for ASD-B2-0121-B
Page 1: ......
Page 13: ...Table of Contents xii Revision June 2010 This page intentionally left blank...
Page 17: ...Chapter 1 Unpacking Check and Model Explanation 1 4 Revision June 2010 ECMA Series Servo Motor...
Page 87: ...Chapter 4 Display and Operation 4 12 Revision June 2010 This page intentionally left blank...
Page 131: ...Chapter 6 Control Modes of Operation 6 22 Revision June 2010 Time Domain...
Page 267: ...Chapter 8 MODBUS Communications 8 18 Revision June 2010 This page intentionally left blank...
Page 271: ...Chapter 9 Maintenance and Inspection 9 4 Revision June 2010 This page intentionally left blank...
Page 291: ...Chapter 11 Specifications 11 8 Revision June 2010 11 3 Servo Motor Speed Torque Curves...