Chapter 7 Servo Parameters
7-14
Revision June 2010
5: V_BUS voltage (+/-8Volts / 450V)
6: Reserved
7: Reserved
Please note: For the setting of analog output voltage proportion, refer to the P1-04
and P1-05.
Example:
P0-03 = 01(CH1 is speed analog output)
Motor speed = (Max. motor speed × V1/8) × P1-04/100, when the output voltage
value of CH1 is V1.
P0 - 04
■
Reserved (Do Not Use)
P0 - 05
■
Reserved (Do Not Use)
P0 - 06
■
Reserved (Do Not Use)
P0 - 07
■
Reserved (Do Not Use)
P0 - 08
★
TSON
Servo Startup Time
Address: 0010H, 0011H
Default: 0
Related Section: N/A
Applicable Control Mode: ALL
Unit: Hour
Range: 0 ~ 65535
Data Size: 16-bit
Display Format: Decimal
P0 - 09
★
CM1
Status Monitor 1
Address: 0012H, 0013H
Default: N/A
Related Section:
Applicable Control Mode: ALL
Section 4.3.5
Unit: N/A
Range: N/A
Data Size: 32-bit
Display Format: Decimal
Settings:
This parameter is used to provide the value of one of the status monitoring
functions found in P0-02. The value of P0-09 is determined by P0-17 (desired drive
status) through communication setting or the keypad. The drive status can be read
from the communication address of this parameter via communication port.
For example:
Set P0-17 to 3, then all consequent reads of P0-09 will return the motor feedback
Summary of Contents for ASD-B2-0121-B
Page 1: ......
Page 13: ...Table of Contents xii Revision June 2010 This page intentionally left blank...
Page 17: ...Chapter 1 Unpacking Check and Model Explanation 1 4 Revision June 2010 ECMA Series Servo Motor...
Page 87: ...Chapter 4 Display and Operation 4 12 Revision June 2010 This page intentionally left blank...
Page 131: ...Chapter 6 Control Modes of Operation 6 22 Revision June 2010 Time Domain...
Page 267: ...Chapter 8 MODBUS Communications 8 18 Revision June 2010 This page intentionally left blank...
Page 271: ...Chapter 9 Maintenance and Inspection 9 4 Revision June 2010 This page intentionally left blank...
Page 291: ...Chapter 11 Specifications 11 8 Revision June 2010 11 3 Servo Motor Speed Torque Curves...