804
Data Control Instructions
Section 3-18
3-18-9 SCALING 3: SCL3(487)
Purpose
Converts signed BCD data into signed binary data according to the specified
linear function. An offset can be input in defining the linear function.
Ladder Symbol
Variations
Applicable Program Areas
Operands
The contents of the five words starting with the first parameter word (P1) are
shown in the following diagram.
Note P1 to P1+4 must be in the same area.
SCL3(487)
S
P1
R
S
: Source word
P1
: First parameter word
R
: Result word
Variations
Executed Each Cycle for ON Condition
SCL3(487)
Executed Once for Upward Differentiation
@SCL3(487)
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program
areas
Step program
areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
∆
Y
∆
X
P1
P1+1
P1+2
P1+3
P1+4
15
0
15
0
15
0
15
0
15
0
Offset of linear function
8000 to 7FFF (signed binary)
0001 to 9999 (BCD)
8000 to 7FFF (signed binary)
Maximum conversion
8000 to 7FFF (signed binary)
Minimum conversion
8000 to 7FFF (signed binary)
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...