![background image](http://html1.mh-extra.com/html/omron/sysmac-cs-series/sysmac-cs-series_reference-manual_742030915.webp)
875
High-speed Counter/Pulse Output Instructions
Section 3-21
Ladder Symbol
Variations
Applicable Program Areas
Operands
C1: Control Data
The function of PRV2(883) is determined by the control data, C1.
Note The second digit of C (
@
) specifies the units and the third digit (
*
) specifies
the frequency calculation method.
C2: Pulses per Revolution
Specifies the number of pulses per revolution (0001 to FFFF hex).
D: First Destination Word
The PV is output to D or to D and D+1.
Operand Specifications
PRV2
C1
C2
D
C1: Control data
C2: Pulses per revolution
D: First destination word
Variations
Executed Each Cycle for ON Condition
PRV2(883)
Executed Once for Upward Differentiation
@PRV2(883)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
C1
PRV2(883) function
0
@
*
0 hex
(See note.)
Converts frequency to rotation speed.
0001 hex
Converts counter PV to total number of revolutions.
C1
0
Conversion Type
0 hex: Frequency to speed
1 hex: Counter PV to total revolutions
(When Conversion Type is "Frequency to speed")
Pulse Frequency Calculation Method
0 hex: Standard calculation method
1 hex: High-frequency calculation method, 10-ms sampling (See note.)
2 hex: High-frequency calculation method, 100-ms sampling (See note.)
3 hex: High-frequency calculation method, 1,000-ms sampling (See note.)
(When Conversion Type is "Frequency to speed")
Speed Unit
0 hex: r/min
1 hex: r/s (See note.)
2 hex: r/h (See note.)
D
D+1
0
15
Conversion result (Rightmost 4 digits)
Conversion result (Leftmost 4 digits)
Area
C1
C2
D
CIO Area
---
CIO 0000 to
CIO 6143
CIO 0000 to
CIO 6142
Work Area
---
W000 to W511
W000 to W510
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...