1099
File Memory Instructions
Section 3-26
EM File Memory-related Words and Bits
3-26-2 READ DATA FILE: FREAD(700)
Purpose
Reads the specified data or amount of data from the specified data file in file
memory to the specified data area in the CPU Unit.
Ladder Symbol
Variations
Applicable Program Areas
Operands
C: Control Word
As shown in the following diagram, the first digit indicates whether the source
Accessing File Flag
A34314
ON when file data is actually being accessed.
Use this flag as an execution condition to pre-
vent a file memory instruction from being exe-
cuted while another is in progress.
Number of Data to
Transfer
A346 to
A347
The contents of these words indicate the sta-
tus of data file transfers.
When an FREAD(700) or FWRIT(701) instruc-
tion is executed, the number of words or fields
to be transferred is written to these words. The
value is decremented by 1 as each word or
field is transferred.
A346 contains the rightmost 16 bits and A347
contains the leftmost 16 bits of the 32-bit
binary value.
Name
Address
Operation
EM File Memory For-
mat Error Flag
A34306
ON when there is a format error in the starting
bank of EM file memory.
EM File Format Starting
Bank
A344
Contains the starting bank number of the EM
Area that has been formatted for use as EM
file memory. Contains FFFF when none of the
EM Area has been formatted.
To convert the EM Area for use as file memory,
the PLC Setup’s EM File Memory setting must
be set to 1 and the EM File Memory Starting
Bank (0 to C) must be set. All EM banks from
the starting bank to the last bank will then be
formatted for use as file memory.
Name
Address
Operation
FREAD(700)
C
S1
S2
D
C
: Control word
S1
: Number of words and
First source word
S2
: Filename
D
: First destination word
Variations
Executed Each Cycle for ON Condition
FREAD(700)
Executed Once for Upward Differentiation
@FREAD(700)
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...