![background image](http://html1.mh-extra.com/html/omron/sysmac-cs-series/sysmac-cs-series_reference-manual_742030244.webp)
204
Sequence Output Instructions
Section 3-4
2.
The OUTB(534) instruction turns ON the specified bit when its execution
condition is ON and turns OFF the specified bit when its execution condi-
tion is OFF.
3.
The set and reset inputs for a KEEP(011) instruction must be programmed
with the instruction, but the SETB(532) and RSTB(533) instructions can be
programmed completely independently. Furthermore, the same bit may be
used as the operand in any number of SETB(532) and RSTB(533) instruc-
tions.
3-4-8
SINGLE BIT OUTPUT: OUTB(534)
Purpose
OUTB(534) outputs the status of the instruction’s execution condition to the
specified bit. OUTB(534) can control a bit in the DM Area or EM Area, unlike
OUT.
This instruction is supported by CS1-H, CJ1-H, CJ1M, and CS1D CPU Units
only.
Ladder Symbols
Variations
Note Immediate refreshing is not supported by CS1D CPU Units.
Applicable Program Areas
Operands
D: Word Address
Specifies the word containing the bit to be controlled.
N: Beginning Bit
Specifies the bit to be controlled. N must be #0000 to #000F (&0 to &15).
Operand Specifications
000000
SETB
D00000
&2
000001
RSTB
D00000
&2
Bit 02 of D00000 is turned ON
when CIO 000000 is ON.
Bit 02 of D00000 is turned OFF
when CIO 000001 is ON.
OUTB(534)
D
N
D: Word address
N: Bit number
Variations
Executed Each Cycle for ON Condition
OUTB(534)
Executed Once for Upward Differentiation
Not supported
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification (See note.)
!OUTB(534)
Block program areas
Step program areas
Subroutines
Interrupt tasks
Not allowed
OK
OK
OK
Area
D
N
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A448 to A959
A000 to A959
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...