Timer and Counter Instructions
Section 3-6
Example 2:
Two-stage Counter
When an SV higher than 9999 is required, two counters can be combined as
shown in the following example. In this case, two CNT instructions are com-
bined to make a BCD counter with an SV of 20,000.
Example 3:
ON/OFF Delay
In this example two TIM timers are combined with KEEP(011) to make an ON
delay and an OFF delay. CIO 000500 will be turned ON 5.0 seconds after
CIO 000000 goes ON and it will be turned OFF 3.0 seconds after CIO 000000
goes OFF.
000000
000001
A20011
C0001
000000 LD
000000
000001 AND
1
s
000002 LD
000001
000004 CNT
0001
#0700
000005 LD
C0001
000006 OUT
000202
000003 OR
A20011
Instruction Operands
Address
1 s (1-s clock)
000000 LD
000000
000001 AND
000001
000002 LD
NOT 000002
000003 OR
C0001
000004 OR
C0002
000005 CNT
0001
#0100
000006 LD
C0001
000007 LD
NO 000002
000008 CNT
0002
#0200
000009 LD
C0002
000010 OUT
000203
Instruction Operands