745
Table Data Processing Instructions
Section 3-17
TB+4 through TB+(N–1): Data storage region
The remainder of the stack is used to store data.
Operand Specifications
TB
0
15
TB+1
0
15
TB+2
0
15
TB+3
0
15
PLC memory address of the last
word in the stack (rightmost 4 digits)
PLC memory address of the last
word in the stack (leftmost 4 digits)
Stack pointer (rightmost 4 digits)
(Initial value is the rightmost 4 digits of
the PLC memory address for TB+4.)
Stack pointer (leftmost 4 digits)
(Initial value is the leftmost 4 digits of
the PLC memory address for TB+4.)
15
0
TB+4
TB+(N–1)
Data storage region
Area
TB
C
D
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A448 to A959
A000 to A959
A448 to A959
Timer Area
T0000 to T4095
Counter Area
C0000 to C4095
DM Area
D00000 to D32767
EM Area without bank
E00000 to E32767
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
---
#0001 to #FFFB
(Hexadecimal)
---
Data Registers
---
DR0 to DR15
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...