1171
Other Instructions
Section 3-31
the total must not exceed 40,000 ms. If WDT(094) cannot be executed again if
the cycle has already been extended to 40,000 ms.
Examples
The default maximum cycle time (1,000 ms) is used in this example.
1,2,3...
1.
When CIO 000000 turns ON, the first WDT(094) instruction extends the
maximum cycle time by 300 ms (30
×
10 ms). Thus, the maximum cycle
time is 1,300 ms at this point.
2.
When CIO 000001 turns ON, the second WDT(094) instruction attempts
to extend the maximum cycle time by another 39,000 ms. Since the new
maximum cycle time (40,300 ms) exceeds the upper limit of 40,000 ms, the
extra 300 ms is ignored. As a result, the second WDT(094) instruction ac-
tually extends the maximum cycle time by 38,700 ms.
3.
When CIO 000002 turns ON, the third WDT(094) instruction attempts to
extend the maximum cycle time by another 1,000 ms. Since the maximum
cycle time has already reached the upper limit of 40,000 ms, the third
WDT(094) instruction is not executed.
3-31-5 SAVE CONDITION FLAGS: CCS(282)
Saves the current status of the Condition Flags in a separate area within the
CPU Unit. The current status of the Flags is preserved so that it can be read
(restored) with CCL(283) at a different location in the program, in a different
task, or even in a later cycle.
This instruction is supported by CS1-H, CJ1-H, CJ1M, and CS1D CPU Units
only.
Ladder Symbol
Variations
Applicable Program Areas
Description
When the execution condition is ON, CCS(282) stores the current status of
the Condition Flags (except for the ALWAYS ON and ALWAYS OFF Flags) in
1
2
3
CCS(282)
Variations
Executed Each Cycle for ON Condition
CCS(282)
Executed Once for Upward Differentiation
@CCS(282)
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...