![background image](http://html1.mh-extra.com/html/omron/sysmac-cs-series/sysmac-cs-series_reference-manual_7420301114.webp)
1074
Network Instructions
Section 3-25
3-25-7 EXPLICIT GET ATTRIBUTE: EGATR(721)
Purpose
Sends an information/status read command in an explicit message (Get
Attribute Single, Service Code: 0E hex).
This instruction is supported by only by CS/CJ-series CPU Unit Ver. 2.0 or
later.
Ladder Symbol
Variations
Applicable Program Areas
Operands
S: First word of send message
Specifies the first word of the send message (S to S+3).
EGATR(721)
S
D
C
S: First word of send message
D: First word of received message
C: First control word
Variations
Executed Each Cycle for ON Condition
EGATR(721)
Executed Once for Upward Differentiation
@EGATR(721)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
S
0
0
8
11
12
15
0
7
S+1
0
0
8
11
12
15
0
7
S+2
0
0
8
11
12
15
0
7
S+3
0
0
8
11
12
15
0
7
Class ID (hex)
Instance ID (hex)
Attribute ID (hex)
Destination Node Address
00 to max. node address (hex)
(00 to 3F hex (0 to 63) for DeviceNet)
If the Attribute ID is not used, set it
to FFFF hex. (The Attribute ID
cannot be set to 0000 hex.)
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...