![background image](http://html1.mh-extra.com/html/omron/sysmac-cs-series/sysmac-cs-series_reference-manual_742030818.webp)
778
Data Control Instructions
Section 3-18
Example 2:
Starting PIDAT(191) with
Autotuning
At the rising edge of CIO 000000 (OFF to ON), autotuning will be performed
first if bit 15 of D00209 (C+9) is ON. When autotuning is completed, the calcu-
lated P, I, and D constants are written to C+1, C+2, and C+3. PID control is
then started with the calculated PID constants.
Example 3:
Interrupting Autotuning
Before Completion
Autotuning can be interrupted by turning bit 15 of D00209 (C+9) from ON to
OFF. PID control will be restarted with the P, I, and D constants that were in
effect before autotuning was started.
CIO 000000
PV
SV
MV
PID
0010
D00200
0020
000000
S
C
D
PID control and
autotuning start.
Calculated PID
constants are set.
PID control
AT executing
Bit 15 of
D00209
Time
Time
CIO 000000
PV
SV
PID control starts.
PID control
PID control
AT executing
Bit 15 of
D00209
Time
AT starts
AT is interrupted.
PID control is restarted with
the existing PID constants.
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...