![background image](http://html1.mh-extra.com/html/omron/sysmac-cs-series/sysmac-cs-series_reference-manual_742030928.webp)
888
High-speed Counter/Pulse Output Instructions
Section 3-21
Applicable Program Areas
Operands
P: Port Specifier
The port specifier indicates the port. The parameters set in D and N will apply
to the next SPED(885) or ACC(888) instruction in which the same port output
location is specified.
T: Pulse Type
T specifies the type of pulses that are output as follows:
N and N+1: Number of Pulses
N and N+1 specify the number of pulses for relative pulse output or the abso-
lute target position for absolute pulse in 8-digit hexadecimal.
The actual number of movement pulses that will be output are as follows:
For relative pulse output, the number of movement pulses = the set number of
pulses. For absolute pulse output, the number of movement pulses = the set
number of pulses
−
the PV.
Operand Specifications
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
P
Port
0000 hex
Pulse output 0
0001 hex
Pulse output 1
T
Pulse type
0000 hex
Relative
0001 hex
Absolute
N
N+1
0
15
Lower word with number of pulses
Upper word with number of pulses
Relative pulse output:
0 to 2,147,483,647 (0000 0000 to 7FFF FFFF hex)
Absolute pulse output:
−
2,147,483,648 to 2,147,483,647 (8000 0000 to 7FFF FFFF hex)
Area
P
T
N
CIO Area
---
---
CIO 0000 to CIO 6142
Work Area
---
---
W000 to W510
Holding Bit Area
---
---
H000 to H510
Auxiliary Bit Area
---
---
A448 to A958
Timer Area
---
---
T0000 to T4094
Counter Area
---
---
C0000 to C4094
DM Area
---
---
D00000 to D32766
EM Area without bank
---
---
---
EM Area with bank
---
---
---
Indirect DM/EM
addresses in binary
---
---
@ D00000 to @ D32767
Indirect DM/EM
addresses in BCD
---
---
*D00000 to *D32767
Constants
See descrip-
tion of oper-
and.
See descrip-
tion of oper-
and.
See description of oper-
and.
Data Registers
---
---
---
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...