Network Instructions
Section 3-25
will be transferred to the desired node. Each routing table is made up of a
local network table and a relay network table.
1,2,3...
1.
Local network table
This table shows the unit numbers and network addresses of the nodes
connected to the local PLC.
2.
Relay network table
This table shows the node numbers and network addresses of the first re-
lay nodes to destination networks that are not connected to the local PLC.
Communications to a Host Computer (Host Link)
By issuing a SEND(090), RECV(098), or CMND(490) instruction to a serial
port set to Host Link mode, the necessary Host Link header and terminator
will be attached to the FINS command and the command will be sent to the
host computer.
Note Host Link communications can be sent through the network. In this case, the
FINS command travels through the network normally. When the command
reaches the Host Link system, the necessary Host Link header and terminator
are attached to the FINS command and the command is sent to the host com-
puter.
Serial Gateway Communications to a Component or Host Link Slave
It is possible to send FINS commands (or send/receive data) to a component
or Host Link Slave connected to the PLC through its serial port with the serial
gateway function.
• Sending to a Component
When a CMND(490) instruction is executed to a serial port that supports
the serial gateway function, the serial gateway function converts the com-
mand to a CompoWay/F, Modbus-RTU, or Modbus-ASCII command.
Host computer
Host Link
CPU Unit
Host Link header
Host computer
Host Link
Host computer
Host Link
Host computer connected to
the CPU Unit's built-in port
Host computer connected to a
Serial Communications Board
(CS Series only)
To port
To port
Host computer connected to a
Serial Port Unit
To port
Serial Communications
Unit
Serial Communications
Board
Host Link FCS
and terminator
FINS
command
FINS command
Host Link
Host computer
Host Link header
FINS
command
Host Link FCS
and terminator
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...