1059
Network Instructions
Section 3-25
8.
The maximum node number depends on the network being used. For a
Controller Link, the allowed range is 00 to 20 hexadecimal (0 to 32). Set
the destination node number to FF to broadcast to all nodes; set it to 00 to
transmit within the local node.
9.
When specifying the serial port in the serial gateway function (conversion
to host link FINS), set the destination unit address to the host link unit num-
ber of the destination PLC + 1 (setting range: 1 to 32).
10. Refer to
Automatic Allocation of Communications Ports
on page 1032 for
details on using automatic allocation of the communications port number
(logical port).
11. When the destination node number is set to FF (broadcast transmission),
there will be no response even if bits 12 to 15 are set to 0.
Unit connected to network (not
necessary to specify Unit)
FE hex
Direct specification of the serial
port’s unit address
Serial Communications Unit ports
Port 1: 80 hex + 4
×
unit number
Port 2: 81 hex + 4
×
unit number
Serial Communications Board ports
Port 1: E4 hex (228 decimal)
Port 2: E5 hex (229 decimal)
CPU Unit ports
Peripheral port: FD hex (253 decimal)
RS-232C port: FC hex (252 decimal)
Unit
Unit address setting
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...