1045
Network Instructions
Section 3-25
Applicable Program Areas
Operands
C: First control word
The five control words C to C+4 specify the number of words being transmit-
ted, the destination, and other settings shown in the following table.
Note
1.
The maximum number of words allowed depends on the network being
used. For a Controller Link, the allowed range is 0001 to 03DE (1 to 990
words).
2.
Set the destination network address to 00 to transmit within the local net-
work. When two or more CPU Bus Units are mounted, the network address
will be the unit number of the Unit with the lowest unit number.
3.
The following two methods can be used to send data to the host computer
through a serial port with the host link while initiating communications from
the PLC.
a) Set the destination unit address (bits 00 to 07 of C+2) to the unit ad-
dress of the CPU Unit or Serial Communications Unit/Board and set
the serial port number (bits 08 to 11 of C+1) to 1 for port 1 or 2 for port
2.
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Word
Bits 00 to 07
Bits 08 to 15
C
Number of words: 0001 to maximum allowed
1
(4-digit hexadecimal)
C+1
Destination network address:
00 to 7F (0 to 127)
2, 4
Bits 08 to 11:Serial port number
3
(physical port)
1 hex:
Port 1
2 hex:
Port 2
(Do not set 0, 3, or 4.)
Bits 12 to 15: Always 0.
C+2
Destination unit address: 00 to FE
5
Destination node address:
00 to maximum allowed
6
C+3
No. of retries: 00 to 0F (0 to 15)
Bits 08 to 11:
Communications port number (inter-
nal logic port): 0 to 7, Automatic allo-
cation: F
7
Bits 12 to 15: Response setting
0: Response requested.
8: No response requested.
8
C+4
Response monitoring time: 0001 to FFFF (0.1 to 6553.5 seconds)
(The default setting of 0000 sets a monitoring time of 2 seconds.)
Unit address
(C+2, bits 00
to 07)
Unit
Serial port number
(C+1, bits 08 to 11)
Serial port
00 hex
CPU Unit
1 hex
Built-in RS-
232C port
2 hex
Peripheral
port
10 hex + unit
number
Serial Communications
Unit (CPU Bus Unit)
1 hex
Port 1
2 hex
Port 2
E1 hex
Serial Communications
Board (Inner Board)
(CS Series only)
1 hex
Port 1
2 hex
Port 2
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...