37
Instruction Functions
Section 2-2
MULTI-OUTPUT
TIMER
MTIM
543
(BCD)
MTIMX
554
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
269
COUNTER
CNT
(BCD)
CNTX
546
(Binary)
(CS1-H, CJ1-H,
CJ1M, or CS1D
only)
Output
Required
275
Instruction
Mnemonic
Code
Symbol/Operand
Function
Location
Execution
condition
Page
MTIM(543)
D1
D2
S
D1: Completion
Flags
D2: PV word
S: 1st SV word
SV 7
SV 2
SV 1
SV 0
0
to
to
Timer input
Timer PV (D2)
to
Bit 7
to
Timer PV
Timer SVs
0
Bit 2
Bit 1
Bit 0
MTIM(543)/MTIMX(554) operates a 0.1-s incrementing timer with 8
independent SVs and Completion Flags. The setting range for the
set value (SV) is 0 to 999.9 s for BCD and 0 to 6,553.5 s for binary
(decimal or hexadecimal).
Completion
Flags (D1)
MTIMX(554)
D1
D2
S
D1: Completion
Flags
D2: PV word
S: 1st SV word
CNT
N
S
Count
input
Reset
input
N
:
Counter
number
S
:
Set value
SV
Count input
Counter PV
Completion
Flag
Reset input
CNT/CNTX(546) operates a decrementing counter. The setting range
for the set value (SV) is 0 to 9,999 for BCD and 0 to 65,535 for binary
(decimal or hexadecimal).
CNTX(546)
N
S
Count
input
Reset
input
N: Counter
number
S: Set value
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...