311
Comparison Instructions
Section 3-7
Using CPS(114) Results in the Program
Do not program another instruction between CPS(114) and the instruction
controlled by the Arithmetic Flag because the other instruction might change
the status of the Arithmetic Flag. In this case, the results of instruction B might
change the results of CPS(114).
The immediate-refreshing variation (!CPS(114)) can be used with words allo-
cated to external inputs specified in S
1
and/or S
2
. When !CPS(114) is exe-
cuted, input refreshing will be performed for the external input word specified
in S
1
and/or S
2
and that refreshed value will be compared. (Immediate
refreshing cannot be performed on inputs allocated to Group-2 High-density
I/O Units or Units mounted to Slave Racks.)
Flags
Note In CS1-H, CJ1-H, CJ1M, and CS1D (for Single-CPU System) CPU Units,
these Flags are left unchanged.
In CS1 and CJ1 CPU Units, these Flags are turned OFF.
Precautions
Do not program another instruction between CPS(114) and an input condition
that accesses the result of CPS(114) because the other instruction might
change the status of the Arithmetic Flags.
CPS
S1
S2
A
Incorrect Use of CPS(114)
Instruction
B
Arithmetic Flag
(Example: Equal Flag)
Name
Label
Operation
Error Flag
ER
Unchanged (See note.)
Greater Than Flag
>
ON if S
1
> S
2
.
OFF in all other cases.
Greater Than or Equal Flag
> =
ON if S
1
≥
S
2
.
OFF in all other cases.
Equal Flag
=
ON if S
1
= S
2
.
OFF in all other cases.
Not Equal Flag
<>
ON if S
1
≠
S
2
.
OFF in all other cases.
Less Than Flag
<
ON if S
1
< S
2
.
OFF in all other cases.
Less Than or Equal Flag
< =
ON if S
1
≤
S
2
.
OFF in all other cases.
Negative Flag
N
Unchanged (See note.)
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...