868
High-speed Counter/Pulse Output Instructions
Section 3-21
Flags
Example
When CIO 000000 turns ON in the following example, SPED(885) starts out-
putting pulses from pulse output 0 in Continuous Mode at 500 Hz. When CIO
000001 turns ON, pulse output is stopped by INI(880).
3-21-2 HIGH-SPEED COUNTER PV READ: PRV(881) (CJ1M-CPU21/22/23
Only)
Purpose
PRV(881) reads the following data on the built-in I/O of CJ1M CPU Units.
• PVs: High-speed counter PV, pulse output PV, interrupt input PV in
counter mode.
• The following status information.
Name
Label
Operation
Error Flag
ER
ON if the specified range for P, C, or NV is exceeded.
ON if the combination of P and C is not allowed.
ON if a comparison table has not been registered but
starting comparison is specified.
ON if a new PV is specified for a port that is currently out-
putting pulses.
ON if changing the PV of a high-speed counter is speci-
fied for a port that is not specified for a high-speed
counter.
ON if a value that is out of range is specified as the PV for
an interrupt input in counter mode.
ON if INI(880) is executed in an interrupt task for a high-
speed counter and an interrupt occurs when CTBL(882)
is executed.
ON if executed for a port not set for an interrupt input in
counter mode.
@SPED
#0000
#0000
D00100
01F4
0000
000000
@INI
#0000
#0003
0000
000001
D00100
D00101
Pulse output 0
CW/CCW method, CW, Continuous Mode
Target frequency: 500 Hz
Pulse output 0
Stop pulse output
(Not used.)
Status type
Contents
Pulse output status
Pulse Output Status Flag
PV Underflow/Overflow Flag
Pulse Output Amount Set Flag
Pulse Output Completed Flag
Pulse Output Flag
No-origin Flag
At Origin Flag
Pulse Output Stopped Error Flag
High-speed counter input status Comparison In-progress Flag
PV Underflow/Overflow Flag
PWM(891) output status
Pulse Output In-progress Flag
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...