![background image](http://html1.mh-extra.com/html/omron/sysmac-cs-series/sysmac-cs-series_reference-manual_742030246.webp)
206
Sequence Control Instructions
Section 3-5
the same time as it writes the status of the execution condition (power flow) to
the specified output bit in I/O memory.
When OUTB(534) is programmed between IL(002) and ILC(003), the speci-
fied bit will be turned OFF if the program section is interlocked. (This is the
same as an OUT instruction in an interlocked program section.)
When a word is specified for the bit number (N), only bits 00 to 03 of N are
used. For example, if N contains FFFA hex, OUTB(534) will control bit 10 of
word D.
Note Difference between SETB(532)/RSTB(533) and OUTB(534)
For OUTB(534), the operand bit is turned ON when the input condition turns
ON and is turned OFF when the input condition turns OFF. For SETB(532)
and RSTB(533), the operand bit turns ON or OFF, respectively, when the input
condition turns ON and the operand bit does not change when the input con-
dition turns OFF.
Example
Note Precaution for Index Registers
OUTB(534) is executed even when the input condition turns OFF. Be particu-
larly careful when programming OUT using an indirect index register address.
3-5
Sequence Control Instructions
3-5-1
END: END(001)
Purpose
Indicates the end of a program.
Ladder Symbol
Variations
Applicable Program Areas
000000
OUTB
D00000
&10
Bit 10 of D00000 is turned OFF
when CIO 000000 is OFF.
MOVR
D100
IR0
Input condition
OUTB
,IR0
&15
When the input condition is OFF,
MOVR(560) is not executed, but
OUTB(534) is executed for the address
stored in the index register.
END(001)
Variations
Executed Each Cycle for ON Condition
END(001)
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
Not allowed
Not allowed
Not allowed
OK
Summary of Contents for SYSMAC CS Series
Page 2: ......
Page 4: ...iv ...
Page 30: ...xxx ...
Page 186: ...146 List of Instructions by Function Code Section 2 4 ...
Page 1320: ...1280 Model Conversion Instructions Unit Ver 3 0 or Later Section 3 35 ...
Page 1390: ...1350 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...
Page 1391: ...1351 Appendix A ASCII Code Table ASCII SP Four leftmost bits Four rightmost bits ...
Page 1392: ...1352 ASCII Code Table Appendix A ...
Page 1404: ...1364 Revision History ...